QYC-12kV-630A Circuit Breaker for GIS

QYC-12kV-630A Circuit Breaker for GIS

QYC-12kV-630A Circuit Breaker for GIS
Here we provide circuit breaker QYV-12kV-630A is a breaker installed in GIS system, with rated current 630A and voltage 12kV, with the latest spring motorized operation mechanism and more than 10,000 time mechanical life.
ConsultConsult immediately
Hotline 86-15558719966

Detailed description

  • Description

GIS circuit breaker QYV-12kV-630A


Summay

There are 3 types circuit breakers for different types of GIS cabinets, QYV-/QYV--ABB/QYV--OM are match with Schneider/ABB/Ormazabal GIS system, with rated current 630A, 800A, 1250A (ABB/Ormazabal).

Can equip Isolation Switch & Earthing Switch together.


1. Altitude ≤1,000m, quake's strength≤8 grade

2. Temperature -40℃~+140℃

3. Relevant daily & monthly humidity≤90%

4. Installation place should avoid distinct vibration, no water vapor, corrosion, salt fog, dust, flamable and exposion hazzard.


Main parameters

Model No. QYV-12kV-630A QYV-12kV-1250A QYV-24kV-630A QYV-24kV-800A QYV-12kV-630A-ABB QYV-12kV-1250A-ABB
QYV-12kV-630A-OM QYV-12kV-1250A-OM
Rated Frequency (Hz)
50
Rated Current (A)
630 1250 630 800 630 1250
630 1250
Rated Voltage (kV) 12 12 24 24 12 12 12 12
Rated Short Circuit Withstand Current (kA)
20/25
Rated Peak Withstand Current (kA)
50
Rated Short Circuit Duration (S)
4S-20kA/3S-25kA
Rated Short Circuit Open/Close Current(kA)
50
Mechanism Endurance (Times)
10,000
Rated operating sequence
O-0.3s-CO-180s-CO


Mechanical parameters

No.
Item Parameter
1 Main circuit resistance
≤30μΩ
2 Overtravel 2-3 mm
3 Opening distance 8-10 mm
4 Bouncing time ≤2 ms
5 Average opening speed 0.6-1.4 m/s
6 Average closing speed 0.4-1.1 m/s
7 Closing asynchronism ≤2 ms
8 Opening asynochronism ≤ 2ms

Outline

GIS circuit breaker 12kV-630A