QYC-12kV-630A Circuit Breaker for GIS
Here we provide circuit breaker QYV-12kV-630A is a breaker installed in GIS system, with rated current 630A and voltage 12kV, with the latest spring motorized operation mechanism and more than 10,000 time mechanical life.
Here we provide circuit breaker QYV-12kV-630A is a breaker installed in GIS system, with rated current 630A and voltage 12kV, with the latest spring motorized operation mechanism and more than 10,000 time mechanical life.
Consult
Hotline 86-15558719966
Detailed description
- Description
GIS circuit breaker QYV-12kV-630A
Summay
There are 3 types circuit breakers for different types of GIS cabinets, QYV-/QYV--ABB/QYV--OM are match with Schneider/ABB/Ormazabal GIS system, with rated current 630A, 800A, 1250A (ABB/Ormazabal).
Can equip Isolation Switch & Earthing Switch together.
1. Altitude ≤1,000m, quake's strength≤8 grade
2. Temperature -40℃~+140℃
3. Relevant daily & monthly humidity≤90%
4. Installation place should avoid distinct vibration, no water vapor, corrosion, salt fog, dust, flamable and exposion hazzard.
Main parameters
Model No. | QYV-12kV-630A | QYV-12kV-1250A | QYV-24kV-630A | QYV-24kV-800A | QYV-12kV-630A-ABB |
QYV-12kV-1250A-ABB |
QYV-12kV-630A-OM |
QYV-12kV-1250A-OM |
|
Rated Frequency (Hz) |
50 |
||||||||
Rated Current (A) |
630 | 1250 | 630 | 800 | 630 |
1250 |
630 |
1250 |
|
Rated Voltage (kV) | 12 | 12 | 24 | 24 | 12 | 12 | 12 | 12 | |
Rated Short Circuit Withstand Current (kA) |
20/25 | ||||||||
Rated Peak Withstand Current (kA) |
50 | ||||||||
Rated Short Circuit Duration (S) |
4S-20kA/3S-25kA |
||||||||
Rated Short Circuit Open/Close Current(kA) |
50 |
||||||||
Mechanism Endurance (Times) |
10,000 |
||||||||
Rated operating sequence |
O-0.3s-CO-180s-CO |
Mechanical parameters
No. |
Item | Parameter |
1 |
Main circuit resistance |
≤30μΩ |
2 | Overtravel | 2-3 mm |
3 | Opening distance | 8-10 mm |
4 | Bouncing time |
≤2 ms |
5 | Average opening speed | 0.6-1.4 m/s |
6 | Average closing speed | 0.4-1.1 m/s |
7 | Closing asynchronism |
≤2 ms |
8 | Opening asynochronism |
≤ 2ms |
Outline
- QYC-12kV-630A Circuit Breaker for GIS
- QYV-12kV-1250A Circuit Breaker of GIS
- QYV-24kV-630A GIS Circuit Breaker
- QYV-24kV-800A GIS Circuit Breaker
- QYV-12kV-630A-OM Circuit Breaker for Ormazabal GIS
- QYV-12kV-1250A-OM Circuit Breaker for Ormazabal GIS
- Isolated Switch for GIS Circuit Breaker ABB version
- Epoxy Resin Insulated Accessories for circuit breaker
Our Products